Type | BKFR-50/220 | BKFR-71/220 | BKGR-70/220 | BKGR-120/380 | |
Ex rate | Ex d e ib nC IIB T4 Gc | ||||
Cooling capacity | W | 5275 | 6448 | 7250 | 12200 |
BTU | 18000 | 24000 | 24000 | 40000 | |
Heating capacity (W) | 5600 | 6600 | 8000 | 14500 | |
Rated voltage/Frequency [V/Hz] | 220/50 | 220/50 | 220/50 | 380/50 | |
Input Power [P] | 2P | 3P | 3P | 5P | |
Cooling input power/current [W/A] | 1752/8.2 | 2186/10.5 | 2200/10.0 | 4380/8.9 | |
Heating input power/current [W/A] | 1647/7.5 | 1886/8.6 | 2600/11.3 | 5000/8.9 | |
Application areas (m²) | 22~27 | 27~34 | 27~32 | 50~80 | |
Sound level [dB] | Indoor unit | 43 | 44 | 43/48 | 52 |
Outdoor unit | 54 | 55 | 56 | 56 | |
Outline dimensions | Indoor unit | 1100*358*294 | 1100*358*294 | 1720*500*300 | 1870*581*395 |
L*W*H [mm] | Outdoor unit | 860*665*330 | 860*665*330 | 980*790*427 | 1250*1032*412 |
Control box | 420*350*178 | 420*350*178 | 300*250*165 | 300*250*165 | |
Weight [kg] | Indoor unit | 16 | 16 | 44 | 63 |
Outdoor unit | 54 | 78 | 68 | 112 | |
Control box | 21.2 | 21.2 | 6 | 7 |
① Z one 1 and Zone 2
② For explosion-proof tank air conditioner, both cooling-only and cooling & heating products in T1, T2,and T3 are available, to meet different requirements of low, medium and high-temperature zones in the world.
③ Explosion-proof tank air conditioner is based on renowned brand, by taking explosion-proof measures to indoor and outdoor units. Measures to outdoor unit:by taking special technics and control, conduct explosion-proof treatment to intemal control units, compressor, outdoor fan motor, protective system, heat-removal system, cooling system, etc. Besides, explosion-proof control box and sensor system are applied with intrinsic safety. The outline dimensions and installation are the same as the prototype after explosion proof treatment. Indoor unit: by taking special technics and control, dismantle intemal electric control units and re-design explosion-proof structure which enables explosion-proof control box separated. Remote controller and sensor system are applied with intrinsic safety. The outline dimensions and installation are the same as the prototype after explosion-proof treatment.